• +420 778 066 566
  • This email address is being protected from spambots. You need JavaScript enabled to view it.

PLA34RG power quality analyser cl. S

A power quality analyser designed according the norm EN 61000-4-30 class S with three voltage and four current inputs for measurement of electrical parameters in LV and MV systems. PLA34RG is built on a 32 bit RISC processor that provides sufficient processing capabilities for real-time measurement and calculation of all parameters and values. Continuous sampling of the voltage and current inputs at 40 kHz guarantees the highest accuracy. The PLA34RG is an instrument for power quality monitoring according to the norm EN 50160.

PLA34RG
fa fa-cogs
  • sampling frequency 40 kHz
  • current sensing via Rogowski coils
  • U accuracy 0.2
  • communication interfaces Ethernet, USB, RS485
  • communication protocols Modbus RTU, Modbus TCP, SNTP, SMTP, FTP, HTTP, MTP, MQTT
  • RS485 Modbus gateway
  • 2 x digital I/O
  • 3 voltage and 4 current inputs
fas fa-chart-bar
  • measuring according IEC 61000-4-30 ed.3 cl. S
  • harmonics, interharmonics EN 61000-4-7 up to 64th
  • filcker measurement according EN 61000-4-1
  • suitable for PQ reports EN 50160
  • transient detection > 25 μs events detection > 10 ms
  • avg, max, min recorded value
  • EN 50160, PGC PQ logging
fas fa-layer-group
  • on board logging Flash memory 1GB
  • WWW-server and email notification
  • DIN rail mounting design
  • PMS SW for configuration, monitoring and evaluation
  • universal auxiliary supply voltage
  • MQTT support PQDIF export

Function

Voltage and current signals are digitalized by high class A/D converter and computing with RISC microprocessor. Efective values are computed continuously in 200 ms (10 periods) windows. Independently on this computing is for events detection each 10ms counted efective value of U and I. Another absolutely independent part is transient detection that are directly detected from samples of digitalized U and I.

IEC 61000-4-30 ed.3 cl. S

PQ analyzer PLA34 measures according the standard IEC 61000-4-30 ed. 3 class S. Such type of analyzers are used in applications where there is necessary precise measurement for power quality evaluation according norms EN 50160, EN 61000-4-7 and EN 61000-4-15.

Digital integrator

Digital integrator for current range change is integrated inside the instrument PLA34RG. Internal digital integraters offers the following measuring current ranges 10 A, 30 A, 100 A, 300 A, 1 kA, 3 kA, 10 kA.

Image

Modbus gateway

Thanks to the built-in Modbus TCP/IP converter it is possible use the PLA34RG as an Ethernet - Modbus gateway for the connection of instruments with RS485 interfaces and Modbus RTU protocols.

Image

Events

Events are unexpected signal changes with duration from 10 ms up to days. In some instalations these events can cause material damages and economical losts. Norm EN 50160 defines limits of events and its quantity that can appear in electrical grid during a year. PQA PLA34 evaluates following type of events DIP, INT, SWELL, RVC and I_MAX.

 

 
+Události

Transients

Transients are very short events with duration of us, that can cause instruments failure or even their damage. For detection of transients are used samples of signal that depends on sampling frequency of PQA. As high sampling as shorter transients can be detected. Power quality analyser PLA34 use sampling rate 40 kHz that allows to detect transients longer that 25 μs.

 

 
+Tranzienty

Webserver

Device has embedded web server for remote monitoring of the PLA34 instrument over the Internet.

Software

Software PMS - Power Monitor System offers possibility for essential configuration of PLA34. More over it is a tool to defgine recording template, alarms, and defined events and transients limits for PQ evaluation. Another part of PMS SW is used for PQ evaluation and report generation.

MQTT

integration of this protocol into PLA34 allows implementation of instrument into any SW. Measured data are divided into several topics in which user can chose which one want to receive. Measured data are transfered in file format JSON.

Measured parameters

ParameterL1L2L3L4L1-2L2-3L3-1∑L1-L3MaxMinAvgRangeDisplayAccuracy
phase voltagetečkatečkatečka     tečkatečkatečka10...600 V1 V...1 MV0.2%
line-line voltage    tečkatečkatečka tečkatečkatečka18...1000 V0...1 MV0.2%
system frequencytečka       tečkatečkatečka40...70 Hz40...70 Hz10 mHz
currenttečkatečkatečkatečka   tečkatečka tečka0.001...8.5 A1 mA...1 MA1%
CosΦtečkatečkatečka     tečka  0.01L...0.01C0.01L...0.01C1%
Power factortečkatečkatečka    tečkatečka  0.01L...0.01C0.01L...0.01C1%
THDU L-Ntečkatečkatečka     tečkatečkatečka0...999%0...999%5%
THDU L-L    tečkatečkatečka tečkatečkatečka0...999%0...999%5%
THDItečkatečkatečkatečka    tečkatečkatečka0...999%0...999%5%
U harmonicstečkatečkatečka        0...999%0...999%class 1
group of U interharmonicstečkatečkatečka        0...999%0...999%class 1
group of U harmonicstečkatečkatečka        0...999%0...999%class 1
P harmonicstečkatečkatečka        0...999%0...999%class 1
Q harmonicstečkatečkatečka        0...999%0...999%class 1
I harmonicstečkatečkatečkatečka       0...999%0...999%class 1
group of I interharmonicstečkatečkatečkatečka       0...999%0...999%class 1
group of I harmonicstečkatečkatečkatečka       0...999%0...999%class 1
short-term flickertečkatečkatečka     tečka  0.4...10.00.4...10.0class A
long-term flickertečkatečkatečka     tečka  0.4...10.00.4...10.0class A
under-voltagetečkatečkatečka tečkatečkatečka tečkatečkatečka0...100%0...100%0.4%
over-voltagetečkatečkatečka tečkatečkatečka tečkatečkatečka0...100%0...100%0.4%
asymmetry of voltage        tečkatečkatečka0...100%0...100%0.3%
N wire voltage        tečkatečkatečka10...600 V0...1 MV0.2%
K-factortečkatečkatečka           
asymmetry of current        tečkatečkatečka  0.5%
PQ transientstečkatečkatečka          25 μs
PQ eventstečkatečkatečkatečka         10 ms
ripple controltečkatečkatečka tečkatečkatečka tečkatečkatečka   
active powertečkatečkatečka    tečkatečka tečka0...15.3 kW0...9999 GW1%
reactive powertečkatečkatečka    tečkatečka tečka0...15.3 kvar0...9999 Gvar1%
apparent powertečkatečkatečka    tečkatečka tečka0...15.3 kVA0...9999 GVA1%
distortion powertečkatečkatečka    tečkatečka tečka  1%
active energy +/-tečkatečkatečka    tečka   0...9999 GWh0...9999 GWhclass 1
reactive L energy +/-tečkatečkatečka    tečka   0...9999 Gvarh0...9999 Gvarhclass 2
reactive C energy +/-tečkatečkatečka    tečka   0...9999 Gvarh0...9999 Gvarhclass 2

Technical features

ParameetrValue
auxiliary supply voltage85 ... 250 VAC/DC (±10%) or 24 ... 60 VAC/DC (±10%)
self consumption< 5 VA
time uncertinity< 1 s a day
number of I/O2
VT and CT ratio1 ... 750 000
event detection40 kHz
Detekce událostí> 10 ms
transient detection> 25 μs
logger memory1 GB flash
displayLCD
communication interfacesRS485 / LAN / USB
communication protocolsModbus RTU, Modbus TCP, SNTP, SMTP, HTTP, FTP, MTP, MQTT
ambient temperature-25°C ... +70°C
dimensions96 x 96 x 60 mm
weight300 g
protection degreeIP20 rear side / IP54 front panel
related standardsEN 61000-4-30 class A / EN 61000-4-7 / EN 61000-4-15 class A / EN 61557-12
Image

Contact

BMR trading - Hasal s.r.o.
Horní lán 1200/17
779 00 Olomouc
Czech Republic

+420 778 066 566