PLA44 DL
Class A Power Quality analyzer
The PLA44 DL is a Class A power quality analyzer designed for DIN rail installation in LV and MV electrical networks. Compliant with IEC 61000-4-30 Class A, it provides accurate measurement and continuous monitoring of electrical parameters and power quality disturbances.
With 40 kHz sampling, the PLA44 DL detects harmonics, voltage events and fast transients. Advanced data logging and analysis support power quality evaluation according to EN 50160.

- U and I accuracy 0.1
- sampling frequency 40 kHz
- communication interfaces Ethernet, USB, RS485
- communication protocols Modbus RTU, Modbus TCP, SNTP, SMTP, FTP, HTTP, MTP, MQTT
- RS485 Modbus gateway
- 2 x digital I/O
- 3 voltage and 3 current inputs
- measuring according IEC 61000-4-30 ed.3 cl. A
- harmonics, interharmonics EN 61000-4-7 up to 64th
- flicker EN 61000-4-15
- suitable for PQ reports EN 50160
- transient detection > 25 μs
- events detection > 10 ms
- avg, max, min recorded value
- external temperature sensor
- 1 GB onboard flash memory for data logging
- Integrated web server and email notifications
- DIN rail mounting design
- PMS SW for configuration, monitoring and evaluation
- MQTT support
- PQDIF export
- EN50160, IEEE519-2014, PGC, PDC reports
Function
Voltage and current signals are digitalized by high class A/D converter and computing with RISC microprocessor. Effective values are computed continuously in 200 ms (10 periods) windows. Independently on this computing is for events detection each 10 ms counted effective value of U and I. Another absolutely independent part is transient detection that are directly detected from samples of digitalized U and I.
IEC 61000-4-30 ed.3 cl. A
PQ analyzer PLA44 DL measures according the standard IEC 61000-4-30 ed. 3 class A. Such type of analyzers are used in applications where there is necessary precise measurement for power quality evaluation according norms EN 50160, EN 61000-4-7 and EN 61000-4-15. If two devices of class A measures the same signal of voltage and current, measurement results at the same moment have to be same with defined measurement uncertainty.
Events
Events are unexpected signal changes with duration from 10ms up to days. In some installations these events can cause material damages and economical lost. Norm EN 50160 defines limits of events and its quantity that can appear in electrical grid during a year. PQA PLA44 DL evaluates following type of events DIP, INT, SWELL, RVC and I_MAX.
Transients
Voltage transients are short commutation, impulse or oscillatory events in electrical grid. Their source can be inductive load switching, power factor correction instruments, atmospheric events, protection instruments action or malfunction of switching elements in the grid.
PLA44 DL analyzer detects two types of transients. Absolute transients and differential transients.
MQTT
Integration of MQTT protocol into power quality analyzer PLA44 DL allows implementation of instrument to any SW. Measured data are divided into several topics in which user can chose which one want to receive. Measured data are transferred in file format JSON.

Software
Software PMS - Power Monitor System offers possibility for essential configuration of PLA44 DL. More over it is a tool to define recording template, alarms, and defined events and transients limits for PQ evaluation. Another part of PMS SW is used for PQ evaluation and report generation.

Measured parameters
| parameter | L1 | L2 | L3 | L4 | L1-2 | L2-3 | L3-1 | ∑L1-L3 | ∑L1-L4 | Max | Min | Avg | Range | Display | Accuracy |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| phase voltage |
|
|
|
|
|
|
10...600 V | 1 V...1 MV | 0.1% | ||||||
| line-line voltage |
|
|
|
|
|
|
18...1000 V | 0...1 MV | 0.1% | ||||||
| system frequency |
|
|
|
|
40...70 Hz | 40...70 Hz | 10 mHz | ||||||||
| current |
|
|
|
|
|
|
0.001...8.5 A | 1 mA...1 MA | 0.1% | ||||||
| cosφ |
|
|
|
|
0.01L...0.01C | 0.01L...0.01C | 1 % | ||||||||
| power factor |
|
|
|
|
|
0.01L...0.01C | 0.01L...0.01C | 1 % | |||||||
| THDU L-N |
|
|
|
|
|
|
0...99.9% | 0...999% | 1 % | ||||||
| THDU L-L |
|
|
|
|
|
|
0...99.9% | 0...999% | 1 % | ||||||
| THDI |
|
|
|
|
|
|
0...99.9% | 0...999% | 1 % | ||||||
| U harmonicics |
|
|
|
0...99.9% | 0...999% | class 1 | |||||||||
| group of U interharmonics |
|
|
|
0...99.9% | 0...999% | class 1 | |||||||||
| group of U harmonics |
|
|
|
0...99.9% | 0...999% | class 1 | |||||||||
| P harmonics |
|
|
|
0...99.9% | 0...999% | class 1 | |||||||||
| Q harmonics |
|
|
|
0...99.9% | 0...999% | class 1 | |||||||||
| I harmonics |
|
|
|
0...99.9% | 0...999% | class 1 | |||||||||
| group of I interharmonics |
|
|
|
0...99.9% | 0...999% | class 1 | |||||||||
| group of I harmonics |
|
|
|
0...99.9% | 0...999% | class 1 | |||||||||
| short-term flicker |
|
|
|
|
|
|
0.4...10.0 | 0.4...10.0 | class A | ||||||
| long-term flicker |
|
|
|
|
|
|
0.4...10.0 | 0.4...10.0 | class A | ||||||
| under-voltage |
|
|
|
|
|
|
|
|
|
0...100% | 0...100% | 0.2% | |||
| over-voltage |
|
|
|
|
|
|
|
|
|
0...100% | 0...100% | 0.2% | |||
| asymmetry of voltage |
|
|
|
0...100% | 0...100% | 0.15% | |||||||||
| N wire voltage |
|
|
|
10...600 V | 0...1 MV | 0.2% | |||||||||
| K-factor |
|
|
|
||||||||||||
| asymmetry of current |
|
|
|
0.5% | |||||||||||
| PQ transients |
|
|
|
25 μs | |||||||||||
| PQ events |
|
|
|
10 ms | |||||||||||
| ripple control |
|
|
|
|
|
|
|
|
|
||||||
| active power |
|
|
|
|
|
|
0...15.3 kW | 0...999 GW | 0.2% | ||||||
| reactive power |
|
|
|
|
|
|
0...15.3 kvar | 0...999 Gvar | 0.2% | ||||||
| aparent power |
|
|
|
|
|
|
0...15.3 kVA | 0...999 GVA | 0.2% | ||||||
| distortion power |
|
|
|
|
|
|
0.2% | ||||||||
| active energy +/- |
|
|
|
|
0...999 GWh | 0...999 GWh | class 0.5S | ||||||||
| reactive L energy +/- |
|
|
|
|
0...999 Gvarh | 0...999 Gvarh | class 1 | ||||||||
| reactive C energy +/- |
|
|
|
|
0...999 Gvarh | 0...999 Gvarh | class 1 | ||||||||
| temperature |
|
|
|
1°C |
Technical features
| Parameter | Value |
|---|---|
| auxiliary supply voltage | 85 ... 250 VAC/DC (±10%) or 24 ... 60 VAC/DC (±10%) |
| self consumption | < 8 VA |
| time uncertinity | < 1 s a day |
| number of I/O | 2 |
| VT and CT ratio | 1...750 000 |
| sampling rate | 40 kHz |
| event detection | > 10 ms |
| transient detection | > 25 μs |
| logger memory | 1 GB flash |
| display | LCD |
| external temperature sensor | NTC 10 kΩ / 25°C |
| communication interfaces | RS485 / LAN / USB |
| communication protocols | Modbus RTU, Modbus TCP, SNTP, SMTP, HTTP, FTP, MTP, MQTT |
| ambient temperature | -25°C ... +70°C |
| dimensions | 6 DIN modules |
| weight | 400 g |
| protection degree | IP20 rear side |
| related standards | EN 61000-4-30 class A / EN 61000-4-7 / EN 61000-4-15 class A / EN 61557-12 |