TRS2D

Technical features

Supply voltage 12 ... 230 V AC/DC (+10/-15%)
System frequency 50/60 Hz
Power consumption max 1,5 VA
Adjustable time range 0,1 sec ... 10 days
Set pause of Y / Δ reconnection 0,1 ... 1 sec
Type of output contact 1 x changeover
Nominal current of output contact 8 A
Switching power max. AC 2000 VA
Trigger current 15 A
Nominal / max switching voltage 250 VAC / 440 VAC
Mechanical lifetime 3 x 106
Electrical lifetime 1 x 104, 250 VAC, 8 A
Working ambient temperature -20°C ... +55°C
Mounting IEC 60715 (DIN 35mm)
Mounting position any
Electrical strength 4 kV
Maximum input wire diameter 2 x 1,5mm2 or 1 x 2,5mm2
Weight 75 g
Dimensions 90 x 18 x 65 mm
Standards IEC 60255, 56, IEC 61010

Terminal description

TRS2D_terminals
  1. Supply voltage
  2. Output indication
  3. Supply voltage indication
  4. Time setting
  5. Fine time setting
  6. Reconnection time setting
  7. Outputs

Connection diagram

TRS2D_connection